| Model | S6K-LV-DP | S6KL-LV-DP | S10K-LV-DP | S10KL-LV-DP | ||
| Capacity | VA/W | 6000VA/5400W | 10000VA/9000W | |||
| Topology | Double Conversion Online UPS | |||||
| AC Mains Input |
Wiring | 1 phase 3wires ( L / N+PE) | ||||
| Rated Voltage | 208/220/230/240Vac | |||||
| Rated Frequency | 50Hz/60HZ | |||||
| Voltage Range | 90~300VAC±5VAC | |||||
| Frequency Range | (40~70)±0.5Hz | |||||
| Input Power Factor | >0.99 | |||||
| Bypass voltage Range | 115~285VAC | |||||
| Battery & Charger |
Rated Battery Voltage | 144VDC Internal |
192VDC Internal or External |
|||
| Battery Capacity | 12V/7AHx12pcs | External Battery Depends | 12V/7AHx16pcs | External Battery Depends | ||
| Backup Time | >6mins @ Half Load | >6mins @ Half Load | ||||
| Charging Current | standard Model with Internal Battery:1A Long Backup Time Model :4A |
|||||
AC Output |
Wiring | 1 phase 3wires ( L / N+PE) or Dual Phase 4wire L1/N1+L2/N2 +PE |
||||
| Output Voltage | High voltage 208/220/230/240Vac Low Voltage 110/120Vac |
|||||
| Output Frequency | 50/60±4Hz(Sync Mode) / 50/60Hz±0.1%(Free Run) | |||||
| Voltage Regulation | +/-3% | |||||
| Waveform | Pure Sine Wave | |||||
| Distortion (THDV%) |
<2%(Linear Load) | |||||
| <7%(None-Linear Load) | ||||||
| Output Power Factor | 0.9 | |||||
| Over load capability | 10min@105%~125% 60s@125%~150% 0.5S@>150% |
|||||
| Transfer Time | Line Mode - Battery Mode 0ms | |||||
| HMI | LCD DISPLAY | Input Mains Voltage, Frequency, Load level, Operation Mode, Health Status | ||||
| Standards COMMUNICATION |
1. RS232 PORT |
|||||
| Optional Extension Card |
|
|||||
| Operating Environment Endurance |
Temperature range | -10~50oC | ||||
| Relative Humidity | 0-98%(Non-condensing) | |||||
Acoustics Noise |
<55dB @ 1 meters | |||||