Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Low Frequency Online UPS Low Frequency Strar Series LF33 10K-120K(3Ph in/3Ph out)
Key Features
Use advanced 6th generation DSP and full digital control technologies to realize higher system stability.Layered independently-sealed ventilation channel and re-dundant fan, circuit boards with protective paints and a dust filter embedded make it highly efficient to dissipate heat and protect the product effectively under severe environment.
Application
Mainly used in large IDC rooms, bank/securities settlement center, communication network management center, semiconductor product lines and large automation production and its control system. According to the special needs of users was improved, and used in large sports venues, conference room, theater and highway and railway tunnels metal halide lamp lighting system.
Technical Specification
Model | LF33 Series | |||||||||||||
Rectifier Type | 6p | 12p | 6p | 12p | 6p | 12p | 6p | 12p | 6p | 12p | 12P | 12P | 12P | |
Rated Nominal | 10KVA/9KW | 20KVA/18KVA | 30KVA/27KW | 40KVA/36KW | 60KVA/54KW | 80KVA/72KW | 100KVA/90KW | 120KVA/108KW | ||||||
Rated input voltage | 380/400/415VAC 3-phase 4-wire | |||||||||||||
Rated frequency | 50/60HZ | |||||||||||||
Input parameters | ||||||||||||||
Input voltage range | ±25% | |||||||||||||
Input frequency range | 45Hz~65Hz | |||||||||||||
Input soft start function | 0-100% 5-300settable | |||||||||||||
Input power factor | >0.8 | |||||||||||||
Input harmonic current | <20% | |||||||||||||
Bypass | ||||||||||||||
Bypass voltage range | -20%~+15% | |||||||||||||
Bypass frequency range | 50/60HZ±10% | |||||||||||||
Output parameters | ||||||||||||||
Inverter output voltage | 380/400/415VAC 3-phase 4-wire | |||||||||||||
Voltage stability | ±1%(Steady status),±3%(Transient status) | |||||||||||||
Frequency | 50/60Hz | |||||||||||||
Mains power synchronization window | ±5% | |||||||||||||
Actually measured frequency accuracy (internal clock) | 50/60Hz±0.05Hz | |||||||||||||
Output power factor | 0.9(Output 90kW per 100kVA) | |||||||||||||
Transient response time | <5ms | |||||||||||||
Inverter overload capability | At 0.9 power factor, 110% for 1 hour, 125% for 10 minutes and 150% for 60s | |||||||||||||
Short circuit current from inverter | 3ph 1.5ln for 5seconds,1ph 2.9ln for 5seconds | |||||||||||||
DC Voltage | 360/384/432/480VDC | |||||||||||||
Maximum Bypass capability | 1000% for 100ms | |||||||||||||
Phase shift Characteristic | With 100% balanced load | <1° | ||||||||||||
With 100% imbalance load | <1° | |||||||||||||
Total harmonic Distortion (THDv) | 100% linear load | <1% | ||||||||||||
100% non- linear load | <3% | |||||||||||||
System efficiency (full | Up to 94% (inverter efficiency is up to 98%) | |||||||||||||
Rectifier output parameters | ||||||||||||||
Charger output voltage stability | 1% | |||||||||||||
DC ripple voltage | ≤1% | |||||||||||||
Operating environment | ||||||||||||||
Operating temperature range | 0~40°C | |||||||||||||
Storage temperature | -25~70°C(Without battery) | |||||||||||||
Relative humidity | 0~95% No condensation | |||||||||||||
Maximum operating height | ≤Elevation 1000m, for elevation above 1000m, derate by 1% for every increase of 100m | |||||||||||||
Noise (1m) | 58-68dB | |||||||||||||
Protection level | IP20 | |||||||||||||
Standard | Safety: IEC60950-1 IEC62040-1-1 UL1778 EMC IEC62040-2 CLASS C2 EN50091-2 CLASS A Design and Test IEC62040-3 | |||||||||||||
Physical parameters | ||||||||||||||
Weight (kg) | 980 | 1420 | 1200 | 1750 | 1350 | 2000 | 1600 | 2200 | 2100 | 2750 | 3690 | 6390 | 7390 | |
Width(mm) | 900 | 1250 | 1250 | 1640 | 1250 | 1640 | 1640 | 2280 | 2280 | 2280 | 2835 | 3955 | 3955 | |
Depth (mm) | 855 | 855 | 855 | 855 | 855 | 855 | 855 | 855 | 855 | 855 | 1000 | 1090 | 1090 | |
Height (mm) | 1900 | 1900 | 1900 | 1900 | 1900 | 1900 | 1900 | 1900 | 1900 | 1900 | 1950 | 1950 | 1950 | |