Single Phase Online UPS with Latest Tri-Level Inverter Control Tech

Phase: Single Phase
Type: On-line
Protection: Overvoltage
Application: Fire Safety
Classification: Lighting/Power
Standby Time: Standard Machine
Samples:
US$ 100/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2014

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
Queen Star Plus Series 6-10k
Standby UPS
Sine Wave Output UPS
Output Capacity
Large Type
Equipment Mode
Decentralized
Brand
Upsen
Battery Type
Lead Acid Battery
Weight
as Per Model
Transfer Time
Zero Conversion
Battery Voltage
192VDC
Transport Package
Cartons & Wooden Pallet
Specification
CE & ISO Certificate
Trademark
UPSEN
Origin
China
HS Code
8504402000
Production Capacity
50, 000PCS/Month

Product Description

Single Phase Online UPS with Latest Tri-Level Inverter Control Tech

Product Advantages:                                                                                                                                                            
1: Latest Tri-level inverter control tech, makes UPS whole efficiency ≥94%, and improve UPS load capacity to support Air Conditioner, Laser Printer etc sensitive loads.
2: Latest soft switch tech in the boost PFC, enable to reduce the PFC IGBT's Voltage spike and switch loss, and improve the UPS capability to resist lighting and Instantaneous over-voltage.
3: Frequency multiplication controlled PFC circuit to reduce the volume of magnetic components, and makes UPS more smart and efficient.
4: PFC and INV adopts hardware current limit design, effectively accelerate the response time of current limit and improve the reliability of UPS
5: More optimized structure layout, makes the UPS size smaller.
6: More cost-save price                 

Main Features
1:Availability of Different Communication types.
2:Sealed lead acid, maintenance free battery.
3:DSP Technology,  compact design, cost-save price
4:Active input power factor correction (PFC).
5:Protection against all types of power problems.
6:Wide range of input voltage and frequency.
7:Active Load Management, cold start function.
8:0.8 Output Power Factor, Digital LCD Screen, Zero transfer time
9:Support sensitive loads like Air Conditioner, Laser Printer etc.
10:Future growth capability - with minimum additional cost and handling
11:Latest Tri-level inverter control tech, whole UPS high efficiency ≥94%.
12:Sufficient Expansion Slots for USB,AS400,CMC monitoring,SNMP,RS485 and EMD environmen monitoring.
13:Electrical Savings due to substantial decrease of power consumption.

                
Perfect Application
Network, data centre, servers and workstations, control system, communication system, Telecom system, power station,security system, hospital, school, Air Conditioner, Laser Printer, home and office etc.    
 
Queen Star Plus Series 6K - 10K Technical Specification
Index Q6K Plus Q6KL Plus Q10K Plus Q10KL Plus  Comments
Input
Input voltage 
Rated voltage 220VAC  
Phase Single phase with ground  
Turn on 
voltage range
(120±5~274±5)VAC  
Bypass 
voltage range
(60±5~300±5)VAC Could be 
adjusted by software.
Bypass low loss 60VAC~220VAC(default 60VAC)
Bypass 
low comeback
Low loss +5VAC
Bypass 
high loss
220VAC~300VAC(default 300VAC)
Bypass 
high comeback
High loss -5VAC
Line low loss
/comeback
(120±5) VAC /(140±5) VAC load≤50%
(150±5) VAC /(165±5) VAC 50%
(160±5) VAC /(175±5) VAC 80%
Line high loss
/comeback
(274±5)VAC/(260±5)VAC  
Input frequency
Rated frequency 50Hz  
Frequency 
low loss
(40~49) ±0.2Hz(default:46Hz) Could be 
adjusted by software.
Frequency 
low comeback
Frequency low loss +0.5Hz
Frequency 
high loss
(51~60)±0.2Hz(default:54Hz)
Frequency 
high comeback
Frequency high loss -0.5Hz
Input power factor
Input power factor > 0.99 Q6K Plus & Q6KL Plus: 
220VAC, full R load
Q10K Plus & Q10KL Plus: 
full R load
Generator  Support generator input Generator rating
≥2*UPS rating
Input current
Rated current  25A 27A 41A 43A  
Input THDI 10%  
Output protection
Rating 
protection
32A Breaker 50A Breaker  
Output power  
VA/watt 6000/4800 10000/8000  
Rated voltage 220VAC Pure Sine wave
Voltage range 200/208/220/230/240VAC Q6K Plus & Q6KL Plus: 
Could be adjusted 
by software. 
10% derating 
for 208VAC/200VAC.
Voltage regulation ±1%  
Voltage distortion ≤6% Full RCD load
≤2% Full R load
DC offset ≤200mV  
Transient response ≤9% R load 0%~100%~0%
≤6% R load 20%~100%~20%
Transient recovery ≤60ms voltage recovery to 90% Full RCD load
Bypass output 
before turn-on
YES  
Crest ration 3:1  
Output frequency range
Normal mode 1,Same as input frequency(46Hz~54Hz)
2,50Hz(Input frequency>54Hz 
or Input frequency<46Hz)
 
Battery mode (50+0.1) Hz  
Slew rate 1 Hz/Sec  
Efficiency
Normal  mode > 93%  
Battery mode > 91%  
Overload
Normal mode
/battery mode
Overload warning only 105%±5%≤load
1min,then transfer to bypass and alarm. 105%±5%<load≤125%±5%
30S,then transfer to bypass and alarm. 125%±5%<load≤135%±5%
100mS, then transfer to bypass and alarm. load>135%±5%
Automatically 
retransfer
YES  
Short protection
Normal
/battery mode
YES  
Transfer time 0mS  
Battery and charger
Battery
Rated voltage 192VDC  
Type/Rating Sunshine 7AH/12V   Sunshine 9AH/12V    
Battery quantity 16 PCS   16 PCS    
Backup time > 14min    >8min   Half load
Protection
Low alarm voltage
comeback voltage
(180.8V±4V)/ (188.8V±4V)  
Shutdown voltage/
comeback voltage
(176V±4V)/ (184V±4V) (176V±4V)/ (184V±4V) (176V±4V)/ (184V±4V) (176V±4V)/ (184V±4V) Load < 1000W
(152V±4V)/ (160V±4V) (160V±4V)/ (168V±4V) (152V±4V)/ (160V±4V) (160V±4V)/ (168V±4V) Load>= 1000W
DC protection
Overcharge protection
comeback voltage
(249.6V±4V) / (216V±4V)  
Leakage current < 500uA  
Over discharge
protection
14.5h Could be 
set by software
Battery test
Battery weak YES  
Battery fault YES  
Charger
Output voltage (219.2±3)VDC  
Charge time 7 hours to 90% capacity        
Charge current 1A 5.5A 1A 5.5A  
Interface
Alarm silence YES  
DC power turn-on YES  
Automatically 
retransfer
YES  
Environment
Work 
temperature
0ºC~40ºC  
Altitude <1000m  
Audible noise ≤55dB ≤60dB  
Storage 
temperature
-15ºC~45ºC  
Work humidity 20%~95%  
Outline dimension and net weight
L*W*H(mm) 533*260*560 425*190*328 533*260*560 533*260*501  
Net weight
(Kg)