Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
High Efficiency Strar Series HE33 10K-200K |
||||||||||||
Model | HE33 Series UPS | |||||||||||
Capacity (VA) | 10K | 15K | 20K | 30K | 40K | 60K | 80K | 100K | 120K | 160K | 200K | |
Noninal output capacity | 8KW | 12KW | 16KW | 24KW | 32KW | 48KW | 64KW | 80KW | 96KW | 128KW | 160KW | |
Operate type | Double conversion online type | |||||||||||
Input | Nominal voltage | 220V/380, 230/400, 240/415V | ||||||||||
Voltage Tolerance | 380/400/415V±25% | |||||||||||
Frequency | 50Hz/60Hz±5% | |||||||||||
Permitted Frequency Tolerance | ±2% (selectable from ±1% to 5% from the front panel) | |||||||||||
Soft start | 0-100% in 30" (selectable) | |||||||||||
Input power factor | 0.95(with input filter) | |||||||||||
Standard features | Back Feed protection separable bypass line | |||||||||||
Phase | Three phase +N+G | |||||||||||
Output | Voltage | 220V/380, 230/400, 240/415V, ±1% (stable load), ±5%(active load) | ||||||||||
Frequency | 50/60Hz (±5%, AC mode), 50/60Hz (±1%, Battery mode) | |||||||||||
Static stability | ±5% in 19ms | |||||||||||
Distortion | Linear load <3%, non linear load<5% | |||||||||||
Power factor | 0.8 | |||||||||||
Output wave | Pure sine wave | |||||||||||
Crest factor | 3:01 | |||||||||||
Battery voltage | Standard battery voltage | 384V | 432V | 480V | ||||||||
Floating charge | 432V | 486V | 540 | |||||||||
Terminal voltage | 336V | 378V | 420V | |||||||||
Charge current | 1A-50A (Can calculate and set according to battery configuration software) | |||||||||||
Maximum Discharge Current | 28 | 42 | 56 | 85 | 113 | 169 | 225 | 282 | 338 | 381 | 507 | |
Main Function | Active voltage change | 0-100%±5% | ||||||||||
Instant recover time | <10ms | |||||||||||
Imbalance voltage | <±5%,<±1%( Balance load voltage) | |||||||||||
Overload capacity | 125% → 10min,150% → 1min | |||||||||||
Static switch | Automatic | |||||||||||
Protection | UPS over current, short circuit, battery low voltage, over heat | |||||||||||
Cold method | Compel aeration ( temperature control mode) | |||||||||||
Noise | 60-65dB | |||||||||||
Display | LED \ LCD display | |||||||||||
Remote signalling | Voltage-free contacts | |||||||||||
Remote commands | EPO and bypass | |||||||||||
Communication Port (Optional) | double RS232 + remote contacts + 2 communication interface slots | |||||||||||
Alarm | Alarm with buzzer and indicators | |||||||||||
Environment | Temperature: 0-40C Humidity: 0-90% | |||||||||||
*Specification are subject to change without prior notice |