Low Frequency Online UPS LP33 Series 10K-200KVA(3Ph in / 3Ph out)
Key Features:
Application:
Model | LP33 20~30Kva | LP33 40~60Kva | LP33 80~100Kva | LP33 120~200Kva | |
Transference | 0ms Cutless | ||||
Technology | True double-conversion online technology, conversion performed by IGBT | ||||
Input | Voltage | 3*220 / 380Vac ± 25% | |||
Frequency | 50Hz ± 15% | ||||
Conductors | Three phrases + N +E | ||||
Ootput | Voltage(Delectable) | 3*220 / 380Vac ± 1% (More voltage can be selected) | |||
Frequency | 50Hz ± 0.1% | ||||
Waveform | Pure sine wave generated by high frequency PWM inverter | ||||
Harmonic Distortion | <2% linear load / <5% nonlinear load | ||||
Crest Factor | 3:1 | ||||
Power Factor | ≥0.9 | ||||
Overload Regulation | Self-Transference to UPS | ||||
Voltage Regulation | Load balance : ±1% | ||||
Overload Capacity | 125% for 12 minutes / 150% for one minute | ||||
Conductors | Three phrases + N +E | ||||
Battery | Type | Maintenance-free sealed lead-acid battery, 12V*32 bars; 120Kva, 160Kva and 200Kva, 12V*40 bars | |||
Full Load Autonomy | 3 to 15 minutes. Extended-range capability | ||||
Typical Recharge Time | 4 ~ 8 hours, 90% | ||||
Battery Handy | Autotest.Transfer point adjustable battery and alarm setting | ||||
Battery Protection | Fuse protection, Battery switch, Temperature compensation, Regular inspection, Software protection,Overvoltage tripping. | ||||
Rectification | Software protection, Input switch, Overcurrent protection, Temperature protection | ||||
Protection | Hardware Protections | Breaker for input,Output,Battery and bypass. Fast acting fuses in DC,Fans,Redundant power supplies,Temperature,Temperature sensors,On-0 switch and audible alarms. | |||
Bypass | Static solid state,Automatic and manual operation without interruption for maintenance.External bypass(optional) | ||||
Emergency Switch | Remote and / or local EPO | ||||
Supervisory Control and Communication | Frontal Panel | Interactive LCD Display(Touchscreen) | |||
Alarms | Audivle and visual alarm for abnormal conditions | ||||
Communications | RS232,SNMP-RJ45,GPRS module for mobile network remote monitoring | ||||
UPS(L*W*D) | 540*1120*620 | 660*1550*860 | 660*1550*860 | 800*1800*1120 | |
Battery Case(L*W*D) | 270*1125*774 | 432*1550*897 | 432*1550*897 | 650*1800*1004 | |
UPS Weight(KG) | 225 | 437 | 600 | 780 | |
Battery Case Weight(KG) | 59 | 105 | 105 | 142 | |
Temperature | 0ºC ~ 40ºC | ||||
Relative Humidity | 0 ~ 95%, Non condensing | ||||
Noise | <60db at 1.5m from surface of unit | ||||
Altitude | 1000m (height rises every 100m, power decreases 1%, maximum height is 4000m) | ||||
Efficiency | >92% | ||||
*Product Specifications are Subject to Change Without Notice. |