Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Still deciding? Get samples of US$ 100/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rack Mount Star Series RM1K-10K | |||||||||
Model |
RM1K |
RM2K |
RM3K |
RM1KL |
RM2KL |
RM3KL |
RM6KL |
RM10KL |
|
Input |
Phase |
Single Phase with Ground |
|||||||
Nominal Voltage |
110115//120Vac or 220/230/240Vac |
220/230/240Vac |
|||||||
Voltage Range |
60-138VAC or 115 ~ 300VAC |
176 ~ 276VAC |
|||||||
Frequency Range |
46 ~ 54Hz(default), user adjustable within 40~60Hz |
46 ~ 54Hz |
|||||||
Power Factor |
0.97 |
0.98 |
|||||||
Connection |
IEC320-10A inlet |
IEC320-16A inlet |
IEC320-10A inlet |
IEC320-16A inlet |
Terminal Block |
||||
Output |
Phase |
Single Phase |
|||||||
Voltage |
110/115/120Vac or 220/230/240VAC ± 2% |
110/115/120Vac or 220/230/240VAC± 1% |
|||||||
Frequency |
46~54Hz or 50Hz ± 0.2Hz (Line mode) |
46~54Hz (Line mode) |
|||||||
50Hz ± 0.2Hz ( Battery mode) |
50Hz ± 0.05Hz ( Battery mode) |
||||||||
Waveform |
Pure Sine Wave |
||||||||
Power Factor |
0.7/0.8 Optional |
||||||||
Overload Capability |
108%~150% for 30 sec., 150% for 300 ms |
105%~130% for 10 min., |
|||||||
130% for 1 min. |
|||||||||
Current Crest Ratio |
3:01 |
||||||||
Connections |
IEC320 -10A * 4 |
IEC320-10A and |
IEC320 -10A * 4 |
IEC320-10A and |
IEC320-10A * 4 and |
||||
Terminal Block |
Terminal Block |
Terminal Block |
|||||||
Bypass |
Automatic Transfer |
on overload and UPS failure |
|||||||
Before UPS Power-on |
Default "NO", user adjustable to "YES" |
Yes |
|||||||
Voltage Range |
80~264VAC (Default), user adjustable within 80~286VAC |
176 ~ 261VAC |
|||||||
Transfer Time |
0 ms; less than 4 ms from inverter to bypass and vice versa |
Zero |
|||||||
LED /LCD indicators |
Load level / Battery level, Battery , Utility Power, |
||||||||
Inverter, Bypass, Overload, Fault |
|||||||||
Audible Alarm |
Bypass, On battery mode, Battery low, Overload, Fault |
||||||||
Communications |
RS-232 Serial Interface |
||||||||
Intelligent Slot; |
|||||||||
OPTIONS: WEBPOWER SNMP/WEB card, |
|||||||||
AS400 card or WinPower CMC) |
|||||||||
Network Surge Protection |
RJ45 I/O port available for network or Fax/Modem |
||||||||
Environmental |
Operating Temperature |
0 ~ 40°C |
|||||||
Operating Humidity |
20 ~ 90% non-condensing |
||||||||
Main Unit |
Net Weight (Kg) |
16.3 |
10.3 |
11.2 |
9.1 |
11.5 |
12.3 |
18.3 |
20.3 |
Dimensions (W x D x H) mm |
482 x 420 x 88 (2U) |
482 x 420 x 88 (2U) or |
482 x 420 x 88 (2U) |
482.6 x 600 x 130 (3U) |
|||||
(3U Internal Batteries) |
|||||||||
Battery Pack |
Type |
Internal Batteries |
External Battery Pack |
||||||
Nominal DC Voltage |
24/36VDC |
48/72VDC |
72/96VDC |
24/36VDC |
48/72VDC |
72/96VDC |
192/240VDC |
||
Battery Numbers |
2/3Pcs *12V7.2Ah |
4/6Pcs *12V7.2Ah |
6/8Pcs *12V7.2Ah |
Depending on the capacity of |
|||||
& Capacity |
external battery packs |
||||||||
Backup Time (Full load) |
5 min |
7min (with 1 BP) |
5 min (with 1 BP) |
||||||
Recharge Time |
5hrs to 90% |
5hrs to 90% |
5hrs to 90% |
||||||
Charging Current (Max.) |
1.0A |
1.0A |
1.0A |
8A±1A |
4.2A |
||||
Charging Voltage |
41.1Vdc±0.6V |
110Vdc±0.4V |
41.1Vdc±0.6V |
110Vdc±0.4V |
274Vdc±1%V |
||||
Net Weight (Kg) |
--- |
25.3 |
25.3 |
--- |
--- |
--- |
--- |
||
Dimensions (W x D x H) mm |
--- |
482 x 420 x88 (2U) |
482 x 420 x88 (2U) |
--- |
--- |
--- |
--- |