220VAC 1k-10kVA Rack Mount Double Conversion High Frequency Online UPS

Phase: Single Phase
Type: On-line
Protection: Overvoltage
Application: Fire Safety
Classification: Lighting/Power
Standby Time: Standard Machine
Samples:
US$ 100/Piece 1 Piece(Min.Order)
| Request Sample
Customization:

Contact Supplier

Diamond Member Since 2014

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
RT Series
Standby UPS
Sine Wave Output UPS
Output Capacity
Large Type
Equipment Mode
Decentralized
Brand
Upsen
Design
Rack Tower
Display
LED/LCD Indicators
Frequency
50Hz/60Hz
Transfer Time
Zero Ms
Transport Package
Cartons & Wooden Pallet
Specification
CE & ISO Certificate
Trademark
UPSEN
Origin
China
HS Code
8504402000
Production Capacity
50, 000PCS/Month

Product Description

220Vac 1K-10KVA Rack Mount double conversion high frequency online ups
High Frequency Online UPS Rack Tower Star Series RT 1K-10KVA(1Ph in/1Ph out)

Key Features:
1:Hot-swappable battery design
2:Self-detection when UPS start-up
3:Fully digitized microprocessor control
4:Large built-in charger with power factor corrected  
5:Diverse options of accessories, intelligent management
6:friendly and intuitive interface, full protection for the equipment
7:DC start function enables UPS to be started up without AC power supplied
8:Adopting high frequency full bridge topology for high steady performances
9:It provides the best power source guarantee for the load equipments for users
10:High availability UPS features: automatic inverter bypass; hot swappable batteries
11:Sine wave output no matters in AC mode or battery mode can provide sine wave power source with low distortion
12:Active Input Power Factor Correction (PFC), UPS can correct the input power factor. Under full load, the input power factor can reach over 0.95 so that the electric environment of the users will not be polluted
 
Applications

Servers, Military,Medical Systems,Network sensitive electronic equipment,Astronautics,Electronic & Telecom
,Army Technology,Securities System,Medical Systems,Network,Instrumentation etc.
 
Technical Specification
MODEL(RT Series) RT1K RT1KL RT2K RT2KL RT3K RT3KL RT6KL RT10KL
Input Rated Capacity 1KVA/800W 2KVA/1600W 3KVA/2400W 6KVA/4800W 10KVA/8000W
Voltage 90 ± 5 ~290 ± 5Vac 176 ~ 276Vac
Current 6A(max) 12A(max) 16A(max) 31A(max) 60A(max)
Frequency 40 ~ 60 Hz
Power factor Conformity EN60555-2(≥0.95) ≥0.95(MAX)
Output Voltage 220Vac ( 1 ± 2%) 220Vac ( 1 ± 1%)
Current 4.55A 9.1A 13.6A 27.3A 54A
Frequency (50 ± 2)Hz (50 ± 1)Hz
Power Factor 0.8 lag
Waveform Sine Wave
Waveform  Linear ≤ 7% when RCD 100% loading (Non-line)
Distortion Linear ≤ 3% when RCD 100% loading (line)
Overload protection 105%<  <125% → 50s 100%-125%, 1 minutes to
125%<  <150% → 25s  transfer to bypass; >150%,
>150% →  300s  100ms to transfer to bypass
Transfer Time Oms
Type of Battery Sealed lead acid maintenance-free
External Battery Voltage 3x7 Ah 36Vdc 6x7 Ah 72Vdc 8x7 Ah 96Vdc 192Vdc/240Vdc
Working  Operating 0-40ºC
Environment  Temperatures(ºC)
  Relative  0-90(%)
  Temperature(ºC)
  Altitude <1500m
Communication 9pin D trpe comector (RS232)
Size (WXDXH) mm 482x450x88 Standard Type (3U): 482x680x132.5 482x680x132.5
Long Backup Type (2U): 482x450x88
Weight (kg) 14.5 8 22 9.8 26 9.8 20 25