• No Break UPS Power with Copper Isolation Transformer for Electrical Equipment and Hospital
  • No Break UPS Power with Copper Isolation Transformer for Electrical Equipment and Hospital
  • No Break UPS Power with Copper Isolation Transformer for Electrical Equipment and Hospital

No Break UPS Power with Copper Isolation Transformer for Electrical Equipment and Hospital

Phase: Three Phase
Type: On-line
Protection: Short Circuit
Application: Industry
Classification: Lighting/Power
Standby Time: Long-acting Machine
Customization:
Diamond Member Since 2014

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
Legend Strar Series 20kva
Standby UPS
Sine Wave Output UPS
Output Capacity
Large Type
Equipment Mode
Centralized Model
Brand
Upsen or OEM
Display
LCD&LED Display
Transfer Time
0ms
Frequency
46-54Hz or 56-64Hz
Admissible Crest Factor
<1%
Transport Package
Standard Export Wooden Cases
Specification
CE & ISO Certificate
Trademark
UPSEN or OEM
Origin
China
HS Code
8504402000
Production Capacity
5000 PCS/Mounth

Product Description

No Break UPS with Wide input voltage and Copper Isolation transformer

1.Low Frequency Online UPS  is 10k-100k
2.No Break UPS for south America
3.three phase Low Frequency Online UPS  with high quality
4.No Break UPS with Wide input voltage

Key Features
1: Humanized display interface
2: DSP technology guarantees high reliability
3: True online double conversion, equipped with IGBT and output transformer
4: Charging/rectifier/inverter fully digital control technology
5: Intelligent battery management to prolong battery lifecycle
6: Redundant fan design and independent ventilation enhance durable operation under harsh environment
7: Intelligent control of multiple CPU
8: Accept dual-mains input
9: Parallel operation with up to 4 units (option)
10: Variety of communication options available
11: Good after-sale services
 
Technical Specification


LS33 Series 10K - 80Kva
MODEL 10K 20K 30K  40K 60K 80K
CAPACITY 10KVA/8KW 20KVA/16KW 30KVA/24KW 40KVA/32KW 60KVA/48KW 80KVA/64KW
INPUT
Nominal Voltage 3 x 380VAC/400VAC (3Ph + N)
Acceptable Voltage Range 305VAC ~ 460VAC
Frequency 46-54Hz or 56-64Hz
INVERTER
Nominal Voltage 3 x 380VAC/400VAC (3Ph + N)
Precision Stationary: ±1%
 Transitory: ±5% (load variations 100-0-100%)
Frequency 50/60 Hz synchronised ±1 %
With mains absent ±0.1 Hz
Max. Synchronisation Speed ±1 Hz/s
Waveform Pure Sinewave
Total Harmonic Distortion (THDv) <2% (Linear Load)
<5% (Non-linear Load)
Phase Displacement 120º ±1% (balanced load)
120º ±2% (imbalances 50% of the load)
Dynamic Recovery Time 1 cycle at 98 % of the static value
Admissible Overload 110% for 10min; 150% for 60sec ; >160% for 200ms
Admissible Crest Factor 3:1
Admissible Power Factor 0.6~1 (inductive or capacitive)
Imbalance Output Voltage @ 100% Unbalanced Load <1%
Current Limit High overload, short-circuit: RMS Voltage Limit
 High Crest-Factor current: Peak Voltage Limit
STATIC BYPASS
Type Solid state
Voltage 3 x 380VAC/400VAC (3Ph + N)
Frequency 50/60 Hz
Activation Criterion Microprocessor control
Transfer Time Zero
Admissible Overload 150% for 1 hour; 180% for 30sec; >200% for 200ms
Transfer to Bypass Immediate, for overloads above 160%
Retransfer Automatic after alarm clear
MAINTENANCE BYPASS
Type Without interruption
Voltage 3 x 400V (3Ph + N)
Frequency 50/60 Hz
Overall Efficiency Line Mode 90% 91% 92% 93%
Battery Mode 90% 91% 93% 93%
BATTERY & CHARGER
Battery Type and Numbers 12VDC x 16 pcs 12VDC x 32 pcs (29~32 pcs adjustable)
Nominal Battery Voltage 192 VDC 384 VDC (Based on 32pcs batteries)
Charging Method CC/CV
Precision  ±1%
Charging Current Max.: 40 A
Charging Voltage 216 VDC 432 VDC (Based on 32pcs batteries)
PHYSICAL
Dimensions, D x W x H(mm) 656 x 405 x 817 656 x 405 x 941 840 x 432 x 1140 975 x 554 x 1286
Net Weight (Kgs) 180 205 295 330 451 519
* Product specifications are subject to change without further notice              
No Break UPS Power with Copper Isolation Transformer for Electrical Equipment and Hospital
No Break UPS Power with Copper Isolation Transformer for Electrical Equipment and Hospital
No Break UPS Power with Copper Isolation Transformer for Electrical Equipment and Hospital
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now